P080-C~P080-12-C
SiRON
8504401400
Order
Product Attributes
Model | P080-C | P080-12-C |
Dc output voltage | 24V | 12V |
Rated current | 0.63A | 1.25A |
Ripple &Noise(Max) | 150mVp-p | 120mVp-p |
Voltage regulation range | 21.6~27.5V | 10.2~13.8V |
Start &rise time | 1500ms,30ms/230VAC;2000ms,30ms/115VAC(full load) | |
Holding time | 30ms/230VAC;10ms/115VAC(full load ) | |
Input parameter | 90~264VAC/120~373VDC;50/60Hz | |
Efficiency | 86% | 85% |
Input current | 0.5A/115VAC;0.25A/230VAC | |
Power factor | 0.65/115VAC;0.5/230VAC | |
Input current | 45A/230VAC | |
Leakage current | <1.0mA/240VAC | |
Overload protection | Rated power105%~150% | |
Protection mode: When the output voltage is less than 50%, it is in hiccup mode. It can automatically recover after the abnormal load conditions are removed | ||
The output voltage is in constant current mode when it is between 50% and 100%, and it can automatically recover after the abnormal load conditions are removed | ||
Overvoltage protection | have | |
Protection mode: Hiccup protection | ||
Shortcircuit protection | Short circuit between the positive and negative terminals of the output | |
Protection mode: Hiccup mode, automatically recovers after abnormal conditions are removed | ||
Operating environment | -30℃~70℃(Refer to the reduction curve) | |
With stand voltage | Input to output: 1000VAC; Input to ground: 1500VAC; Output to ground 500VAC | |
Insulation impedance | Input to output, input to ground, output to ground 100M Ohms/500VDC/25℃/70%RH | |
Electromagnetic compatibility | GB9254 CLASS A | |
Safety specification | reference GB4943.1-2011 | |
Product size | 17.5×90×54.5(W×H×D) | |
Package | 74g;160pcs/12.9kg/1.09CUFT |